System-sensor CR-6 Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Ausrüstung System-sensor CR-6 herunter. System Sensor CR-6 User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 4
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
D500-48-00 1 I56-1798-009
INSTALLATION AND MAINTENANCE INSTRUCTIONS
BEFORE INSTALLING
This information is included as a quick reference installation guide. If the
modules will be installed in an existing operational system, inform the op-
erator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably
grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The CR-6 Six Relay Control Module is intended for use in an intelligent alarm
system. Each module is intended for Form-C switching applications, which do
not require wiring supervision for the load circuit. A single isolated set of dry
relay contacts is provided for each module, which is capable of being wired
for either normally open or normally closed for each operation. Each module
has its own address. A pair of rotary code switches is used to set the address
of the first module from 01 to 94. The remaining modules are automatically as-
signed to the next five higher addresses. Provisions are included for disabling
a maximum of three unused modules to release the addresses to be used else-
where. Each CR-6 module also has panel controlled green LED indicators. The
panel can cause the LEDs to blink, latch on, or latch off.
CR-6 Six Relay Control Module
SPECIFICATIONS
Normal Operating Voltage: 15-32 VDC
Stand-By Current: 1.45 mA
Alarm Current: 32 mA (assumes all six relays have been switched once and all six LEDs solid on)
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10 to 93% Non-condensing
Dimensions: 6.8˝H × 5.8˝W × 1.0˝D
Accessories: BB-2 Cabinet; BB-6 Cabinet; CH-6 Chassis
Wire Gauge: 12-18 AWG
Relay Current: 30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
CONTENTS INCLUDE:
(6) 1 x 3 Terminal Blocks
(1) 1 x 4 Terminal Blocks
(2) 1¼˝ (32mm) Stand offs
(4) Machine Screws
(1) Shunt (NOTE: For the disable position, not more than one shunt shall be
installed at the same time)
(2) Nuts
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
control panel only.
COMPONENTS
Following are descriptions of the CR-6 mounting frameworks. There are two
mounting options for CR-6 modules:
• Up to six CR-6 modules can be installed on a CH-6 in a BB-6 cabinet
• One or two CR-6 modules can be installed in a BB-2 cabinet
Chassis
The CH-6 chassis is used to mount CR-6 modules in a BB-6 cabinet. It accom-
modates up to six CR-6 modules in a single cabinet row three modules wide
and two modules deep.
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
RELAY CONTACT RATINGS:
I56-1798-009
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC PF = 0.75 Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - CR-6 Six Relay Control Module

D500-48-00 1 I56-1798-009INSTALLATION AND MAINTENANCE INSTRUCTIONSBEFORE INSTALLINGThis information is included as a quick reference installation gui

Seite 2 - C0243-00

FIGURE 1: CH-6 CHASSISThe BB-2 cabinet has a built-in chassis that will accommodate one or two CR-6 modules.FIGURE 2: BB-2 CABINET01234567890786543219

Seite 3 - 4˝ (6.35mm) of

FIGURE 6A: INSTALLATION OF CR-6 MODULE IN A REAR CHASSIS POSITION, METHOD TwO1Step 1: Insert the bottom edge of the CR-6 module down into a rear sl

Seite 4 - 5.8"

D500-48-00 4 I56-1798-009 ©2011 System SensorFCC STATEMENTThis device complies with part 15 of the FCC Rules. Operation is subject to the followi

Kommentare zu diesen Handbüchern

Keine Kommentare