FAASTFire Alarm Aspiration Sensing Technology®3825 Ohio Avenue, St. Charles, Illinois 601741.800.SENSOR2; Fax: 630.377.6495www.systemsensor.comCOMPREH
When the desired changes have been made, select the OK button to close the window.Highlight the pipe (pipe turns from red to grey) then select and dra
Pipe Layout ReportThe Pipe Layout Report generates a report about the site, including informa-tion, such as name, location detector information, confi
FIGURE 24. PIPE WIZARD DETECTOR LOCATION SCREENASP54-01FIGURE 25. PIPE WIZARD DETAILS SCREENThe Pipe Screen prompts for the type of pipe material bein
FIGURE 26. REMOTE MONITORING OF USER INTERFACE PANELFIGURE 27. MONITORING THE TREND GRAPHLive ViewSelect the Monitoring tab in the lower left corner o
FIGURE 31. LOG VIEWLive EventsLive Events allows the viewer to see current activities at a specific FAAST de-vice. The log viewer provides the device
Web Browser AccessCOMPREHENSIVE INSTRUCTION MANUALSCOPEThis section describes how to access the FAAST detector over a local network (LAN) via the Web
LIVE VIEW SCREENA live view of the User Interface Display Panel may be obtained by selecting the Live View tab, as shown in Figure 5.The Live View scr
CommissioningCOMPREHENSIVE INSTRUCTION MANUALSCOPEThis section provides an overview of the commissioning process for a system and describes how the co
CONFIGURING A NEW FAAST SYSTEMIf the FAAST detector has never been configured before, when initially pow-ered it indicates a configuration fault. Begi
TABLE 2. GENERAL FIELD DESCRIPTIONSTABLE 6. ALARM/FAULT RELAY LATCHING CHECK BOX DESCRIPTIONSTABLE 3. DEVICE DATE AND TIME FIELD DESCRIPTIONSTABLE 4.
SS-400-007 2 E56-3621-003 Table of ContentsmAinTenAnce And TroubleShooTing ...26SCOPE ...
ALARM LEVELTHRESHOLD HIGH SENSITIVITYTHRESHOLD LOW SENSITIVITYCURRENT LEVELAlert Alert High Alert Low Acclimate Alert LevelAction 1 Action 1 High Ac
FIGURE 8. TYPICAL STABILIZED FRONT PANEL INDICATORS3. Create a project using an appropriate title, as shown in Figure 9, by select-ing File>New fr
Relay Function TestingThe Relay function can be verified by setting the system into Test mode. The Test mode is initiated through the PipeIQ Live View
SS-400-007 23 E56-3621-003 CommissioningCustomer Name:Project Name:Site Address:Installer Name/Contact information: Date:Commissioning Agent/Conta
SS-400-007 24 E56-3621-003 CommissioningthReshold time delay tRanspoRt timesDay Alert: Predicted: Actual:Action 1: Predicted: Actual:Action 2: Pre
Maintenance and TroubleshootingCOMPREHENSIVE INSTRUCTION MANUALSCOPEThis section provides guidance through maintenance and troubleshooting for the FA
TYPE CONDITION RECOMMENDED ACTIONFault Warning External Monitor Fault signals, but nothing is con-nected to the external monitor relay.Attach the 47 K
PIPEIQ FAAST CONNECTION TROUBLESHOOTING In order to connect to a FAAST device at its default IP address (192.168.1.10) the PC network adapter must be
Parts and AccessoriesCOMPREHENSIVE INSTRUCTION MANUALSCOPEThis section provides information on the parts and accessories available for the FAAST syst
The Pipe SystemCOMPREHENSIVE INSTRUCTION MANUALSCOPEThis section provides details on the physical installation of the pipe network for the FAAST syst
SCOPEThis section provides information for pipe network designers and adminis-trators on the use of the PipeIQ® software program for the FAAST system.
CAPILLARY TUBES AND SAMPLING POINTSA capillary tube is a length of flexible tubing that is connected to the main sampling pipe with a sampling point a
Pipe BendsNever bend pipes, unless absolutely necessary. Use elbows, tees or other fit-tings to change the direction of the pipe.If bending is necessa
Application and DesignCOMPREHENSIVE INSTRUCTION MANUALSCOPEThis section is intended to provide general design and application guidelines for designin
OPEN AREA PROTECTIONCeiling SamplingIn typical ceiling installations, the pipe network is suspended from 1 in. to 1 ft. (25 mm to 300 mm) below the ce
HIGH AIR EXCHANGE AREASTypically, high air exchange areas have some form of mechanical ventilation to maintain constant or cyclical air flow for heati
TABLE 2. HOLE SIZES FOR LARGE DUCTSDUCT WIDTH NO. OF HOLESHOLE SIZE NOMINAL PIPE FLOW RATE (CFM)3 ft. 4 in. (1 m) 6 9/64 in. (3.5 mm)1.77 cfm (50.2
TABLE 5. VIEW MENUMENU CHOICE DESCRIPTIONMonitoring Changes the view of the project to the monitoring screen. (For object levels above the device leve
SITE CONFIGURATION When a new project is created, the factory default settings are used to create all of the objects. Any number of buildings, floors,
Button Lock-OutDepending on the model selected, the button lockout feature may or may not appear. If the button lock out option is not available, this
TABLE 12. DEFAULT NORMAL MODE THRESHOLD VALUESALARM SPECIFY THE THRESHOLD LEVEL IN %FT FOR NORMAL MODEDay Night WeekendAlert 0.012 0.012 0.012Action
FIGURE 11. CONNECT POPUP WINDOWEnter the IP address of the Host (FAAST detector), select either Read-Only or Administrator from the User list. If Admi
BUTTON DESCRIPTION Import an existing floor plan in (.dxf) format. Changes the view of the pipe layout to isometric. Changes the view of the pipe lay
Manuales del propietario y guías del usuario para Hardware Interlogix R1075 Series.
Ofrecemos 1 manuales en pdf Interlogix R1075 Series para descargar gratis por tipos de documentos: Manual de usuario
Marca: Interlogix | Categoria: Hardware | Tamaño: 0.07 MB |
Modelos | Tipo de documento |
---|---|
R1125 Series | Manual de usuario Interlogix R1125 Series User Manual, 2 paginas |
R1125T Series | Manual de usuario Interlogix R1125T Series User Manual, 2 paginas |
DesignLine Recessed Door Contact | Manual de usuario Interlogix DesignLine Recessed Door Contact User Manual, 2 paginas |
IFS SFP Transceiver | Manual de usuario Interlogix IFS SFP Transceiver User Manual, 13 paginas |
R3 IFS Fiber Module | Manual de usuario Interlogix R3 IFS Fiber Module User Manual, 6 paginas |
2251D | Manual de usuario Interlogix 2251D User Manual, 4 paginas |
270D | Manual de usuario Interlogix 270D User Manual [de] [en] [fr] , 5 paginas |
S7711D | Manual de usuario Interlogix S7711D User Manual, 11 paginas |
S7711F2F | Manual de usuario Interlogix S7711F2F User Manual, 9 paginas |
S7712D | Manual de usuario Interlogix S7712D User Manual, 15 paginas |
S713D | Manual de usuario Interlogix S713D User Manual, 9 paginas |
S7714D | Manual de usuario Interlogix S7714D User Manual, 8 paginas |
503H | Manual de usuario Interlogix 503H User Manual, 4 paginas |
517R1 | Manual de usuario Interlogix 517R1 User Manual, 5 paginas |
503R | Manual de usuario Interlogix 503R User Manual [es] [de] [it] [en] , 4 paginas |
517EPS1 | Manual de usuario Interlogix 517EPS1 User Manual, 6 paginas |
Kommentare zu diesen Handbüchern