System-sensor 2551 and 2551T Plug-in Intelligent Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Ausrüstung System-sensor 2551 and 2551T Plug-in Intelligent herunter. System Sensor 2551 and 2551T Plug-in Intelligent User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 4
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
D500-04-00 1 I56-292-05
2551 and 2551T Plug-in Intelligent
Photoelectronic Sensors with
Communications
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read the system wiring and installation
manual, which provides detailed information on sensor
spacing, placement, zoning, and special applications. Cop-
ies of these manuals are available from System Sensor.
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: These detectors must be tested and main-
tained regularly following NFPA 72 requirements. These
detectors should be cleaned at least once a year.
General Description
The model 2551/2551T photoelectronic sensors utilize a
state-of-the-art, optical sensing chamber. These sensors are
designed to provide open area protection, and to be used
with compatible control panels only. Connect detectors
only to compatible control units. (For installation in
Canada, refer to CAN/ULC-S524-M86, Standard for the In-
stallation of Fire Alarm Systems and CEC Part 1, Sec. 32.)
Two LEDs on each sensor light to provide a local 360° vis-
ibility of the sensor indication. The LEDs can be latched
ON by code command from the panel for an alarm indica-
tion. The LEDs can also be unlatched to the normal condi-
tion by code command. Remote LED annunciator
capability is available as an optional accessory (part no.
RA400Z).
Specifications
Diameter: 6.1 inches (15.5 cm) installed in B501B
4.0 inches (10.2 cm) installed in B501
Height: 3.2 inches (8.1 cm)
Add 0.5 inches (1.3 cm) for thermal models
Weight: 9.6 ounces (272 g)
Installation Temperature Range
2551: 32° to 120°F (0° to 49°C)
2551T: 32° to 100°F (0° to 38°C)
Installation Humidity Range: 10% to 93% Relative Humidity
Mounting: B501B flanged base
B501 flangeless base
B501 with RMK400 recessed mounting kit
Maximum Air Velocity: 3000 Ft./Min. (15 m/S)
Voltage Range: 15 to 32 Volts DC Peak
Standby Current: 230
µ
A @ 24 VDC
LED Current: 6.5 mA @ 24 VDC
The 2551T adds a thermal heat collector that will alarm at a
fixed temperature of 135° F.
Wiring Guide
Refer to the installation instructions for the particular plug-
in base being used: 1) for the B501B base (D550-01-01); 2)
for the B501 base (D550-02-00); 3) for the RMK400 used
with the B501 base (D450-07-00). Bases are provided with
screw terminals for power, ground, and remote annunciator
connections (see Figure 1).
NOTE: All wiring must conform to applicable local codes,
ordinances, and regulations.
NOTE: Verify that all sensor bases are installed and that
the wiring polarity is correct at each base.
WARNING
Remove power from the loop before installing sensors.
1. Install sensors:
a. Verify that the sensor type matches the type written
on the label on the base.
b. Set the sensor to a desired address and then write the
address on the label on the base.
c. Place the sensor into the sensor base.
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - Communications

D500-04-00 1 I56-292-052551 and 2551T Plug-in IntelligentPhotoelectronic Sensors withCommunicationsINSTALLATION AND MAINTENANCE INSTRUCTIONSA Division

Seite 2 - CONTROL PANEL

D500-04-00 2 I56-292-05d. Turn the sensor clockwise until it drops into place.e. Continue turning the sensor clockwise until it locksinto place.WARNIN

Seite 3 - D500-04-00 3 I56-292-05

D500-04-00 3 I56-292-05NOTE: If the sensor’s sensitivity limits or the MOD400Rlimits do not appear on the back of the sensor, theMOD400R is not suitab

Seite 4

D500-04-00 4 I56-292-05 © System Sensor 1996Three-Year Limited WarrantySystem Sensor warrants its enclosed smoke detector to be free from de-fects in

Kommentare zu diesen Handbüchern