PDRP-1002SeriesAgent Release Control SystemInstruction Manual3825 Ohio AvenueSt. Charles, IL 601741-800-SENSOR2Fax: (630) 377-6495PN 51135:B0
1. Product Description DIP Switch Functions10PDRP-1002 Instruction Manual PN 51135:B0 04/06/01DIP Switch FunctionsThe table below describes the DIP
Options 1. Product DescriptionPDRP-1002 Instruction Manual PN 51135:B0 04/06/0111Remote Annunciator - RZA-4X The Remote Annunciator mounts on a stan
1. Product Description Specifications12PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Specifications AC PowerPDRP-1002: 110/120 VAC, 50/60 Hz, 1.2
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01132. InstallationCabinet MountingCarefully unpack the system and check for shipping damage.Select a
2. Installation Cabinet Mounting14PDRP-1002 Instruction Manual PN 51135:B0 04/06/01The figure below shows the exterior dimensions and mounting hole
Installing Optional Voltmeter/Ammeter 2. InstallationPDRP-1002 Instruction Manual PN 51135:B0 04/06/0115Installing Optional Voltmeter/AmmeterTo moni
2. Installation Power Connections16PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Power ConnectionsWARNING: Do not apply any type power to this c
Power-limited Wiring Requirements 2. InstallationPDRP-1002 Instruction Manual PN 51135:B0 04/06/0117Observe polarity when connecting the batteries.
2. Installation Initiating Device Circuits18PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Initiating Device CircuitsThe control panel provides tw
Initiating Device Circuits 2. InstallationPDRP-1002 Instruction Manual PN 51135:B0 04/06/0119Four-Wire Smoke Detector ConnectionsA maximum of 200mA
LimWarLg.p65 01/10/2000An automatic fire alarm system–typically made up of smokedetectors, heat detectors, manual pull stations, audible warn-ing d
2. Installation Output Circuits20PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Output Circuits Notification Appliance CircuitsThe control panel p
Output Circuits 2. InstallationPDRP-1002 Instruction Manual PN 51135:B0 04/06/0121Releasing CircuitsCAUTION: To prevent accidential discharge, conne
2. Installation Powering External Devices22PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Alarm Relay Circuit One Form-C dry contact alarm relay i
Optional Modules 2. InstallationPDRP-1002 Instruction Manual PN 51135:B0 04/06/0123Optional ModulesOverviewThe control panel has two module connecto
2. Installation Optional Modules24PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Installation - Lower PositionTo install either the 4XTM, 4XZM or
Optional Modules 2. InstallationPDRP-1002 Instruction Manual PN 51135:B0 04/06/0125Setup and ConfigurationTransmitter Module - 4XTMConnect a Remote
2. Installation Optional Modules26PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Zone Relay Module - 4XZMRelay #1 through #4 on this module have s
Optional Modules 2. InstallationPDRP-1002 Instruction Manual PN 51135:B0 04/06/0127LED Interface Module - 4XLMConnect the terminals on TB1 of the LE
2. Installation Setting Mode of Operation28PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Setting Mode of OperationSelect operating mode by settin
Setting Mode of Operation 2. InstallationPDRP-1002 Instruction Manual PN 51135:B0 04/06/0129Switch #2 - Supervisory/Releasing ServiceSet the functio
LimWarLg.p65 01/10/2000WARNING - Several different sources of power can be con-nected to the fire alarm control panel. Disconnect all sourcesof po
2. Installation Setting Mode of Operation30PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Zone Relay Module ConfigurationRelay #1, #2, #3 and #4 o
Power-Up Procedure 2. InstallationPDRP-1002 Instruction Manual PN 51135:B0 04/06/0131Power-Up ProcedureWARNING: Prior to energizing this panel, not
2. Installation Power-Up Procedure32PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Notes
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01333. System OperationWARNING: When used for CO2 releasing applications, observe proper precautions
3. System Operation Control Switches34PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Control Switches Figure 22 Control Panel SwitchesTone Silenc
Piezo 3. System OperationPDRP-1002 Instruction Manual PN 51135:B0 04/06/0135PiezoThe piezo (local buzzer) generates different tone patterns for diff
3. System Operation Last Event Recall36PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Last Event RecallLast Event Recall allows the user to displa
System Events 3. System OperationPDRP-1002 Instruction Manual PN 51135:B0 04/06/0137Single Zone in Alarm (Cross Zone) ConditionUpon actuation of a s
3. System Operation System Events38PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Notes
PDRP-1002 Instruction Manual PN 51135:B0 04/06/0139Appendix A: Secondary Power CalculationsStandby Battery RequirementsThe Standby Battery Current o
NFPA Standards4PDRP-1002 Instruction Manual PN 51135:B0 04/06/01NFPA StandardsThis control panel complies with the following NFPA standards: • NFPA
Appendix A: Secondary Power Calculations Calculating the Battery Capacity40PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Calculating the Battery
PDRP-1002 Instruction Manual PN 51135:B0 04/06/0141Appendix B: Compatible DevicesTwo-wire Smoke Detectors, UL ListedUse the two-wire detectors liste
Appendix B: Compatible Devices Four-wire Smoke Detectors, UL Listed42PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Four-wire Smoke Detectors, UL
Notification Appliances, UL Listed Appendix B: Compatible DevicesPDRP-1002 Instruction Manual PN 51135:B0 04/06/0143Notification Appliances, UL List
Appendix B: Compatible Devices Notification Appliances, UL Listed44PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Table 6 Notification Appliances
Door Holders, UL Listed Appendix B: Compatible DevicesPDRP-1002 Instruction Manual PN 51135:B0 04/06/0145Door Holders, UL ListedUse the Door Holders
Appendix B: Compatible Devices 24 VDC Relays, UL Listed46PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Notes
PDRP-1002 Instruction Manual PN 51135:B0 04/06/0147Appendix C: NFPA Standard-Specific RequirementsMinimum System RequirementsThe control panel has b
Appendix C: NFPA Standard-Specific Requirements Digital Alarm Communicator/Transmitter - Noti-Fire 911AC48PDRP-1002 Instruction Manual PN 51135:B0 0
Universal Digital Alarm Communicator - 411UDAC Appendix C: NFPA Standard-Specific RequirementsPDRP-1002 Instruction Manual PN 51135:B0 04/06/0149Uni
Table of ContentsPDRP-1002 Instruction Manual PN 51135:B0 04/06/015Table of ContentsNFPA Standards...
Appendix C: NFPA Standard-Specific Requirements Local Energy Municipal Box50PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Local Energy Municipal
Remote Station Receiver - RS82-9 Appendix C: NFPA Standard-Specific RequirementsPDRP-1002 Instruction Manual PN 51135:B0 04/06/0151Remote Station Re
Appendix C: NFPA Standard-Specific Requirements Remote Station Receiver - RS82-952PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Notes
PDRP-1002 Instruction Manual PN 51135:B0 04/06/0153Appendix D: Testing & MaintenanceTestingInspectionPerform the following prior to applying pow
Appendix D: Testing & Maintenance Troubleshooting54PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Table 9 Troubleshooting Table Symptom Pro
IndexPDRP-1002 Instruction Manual PN 51135:B0 04/06/0155IndexNumerics110/120 VAC 12220/240 VAC 12411UDAC 47, 494XLM LED Interface Module 11, 234XMM
Index56PDRP-1002 Instruction Manual PN 51135:B0 04/06/01GGeneral Alarm 30ground fault 33, 50IIndicating Circuit #1 53initial alarm test 53initiating
IndexPDRP-1002 Instruction Manual PN 51135:B0 04/06/0157Rrail 24rail, backbox 13, 14red wire 17regulated power 22relay contacts 49Relay, System Alar
58PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
PDRP-1002 Instruction Manual PN 51135:B0 04/06/0159
Table of Contents6PDRP-1002 Instruction Manual PN 51135:B0 04/06/01Zone Relay Module - 4XZM ...
Limited WarrantySystem Sensor® warrants its products to be free from defects in materials and workman-ship for eighteen (18) months from the date of
PDRP-1002 Instruction Manual PN 51135:B0 04/06/0171. Product DescriptionOverviewThe PDRP-1002 Agent Release Control System has been designed as a co
1. Product Description Circuits8PDRP-1002 Instruction Manual PN 51135:B0 04/06/01CircuitsInput CircuitsDetector Zone 1 (Style B/D)Detector Zone 2 (S
Control Panel 1. Product DescriptionPDRP-1002 Instruction Manual PN 51135:B0 04/06/019Control Panel Figure 1 Control PanelSW1TB1TB2TB3TB4JP1GENALM